Burner Control

Type : SM 152N.2

Burner Control

Code : 24283961

Type : SM152N.2

Description

Power supply                                          :    230V 50/60Hz

Operating temperature range                    :    -20°C +60°C

Humidity                                                 :    95% max at 40°C

Protection degree                                     :    socket NG IP 40 (after installation)

                                                                   socket P/R IP 00

Times                                           

                                                                   waiting/pre

-purge time (TW)                                     :    1,5..40 s

TW for type SM152N                                      3..40 s safety

time at start-up (TS)                                 :    3..60 s

- Response time in case of flame failure              < 1 s

The times appearing on the product label correspond to guaranteed values. Actual times may differ from declares ones, as waiting and pre-purge time may be longer and safety time shorter than their nominal values.

Power consumption at start-up                   :    atmospheric burner                   10VA

                                                                    atmospheric fan-assisted burner 12VA

Power consumption during operation           :    atmospheric burner                     7VA

                                                                    atmospheric fan-assisted burner    9VA

Close [X] ไลน์12-1-65